This command reports the current situation of the device:
[13:42:55] ABILIS_CPX:d d ups
RES:Ups -----------------------------------------------------------------------
Uninterruptable_Power_Supply_device
USB-STATE:CONNECTED UPTIME:41 days 21:09:37 (13/07/2017 14:49:33)
POWER-SOURCE:MAIN BATTERY:NOT-PRESENT
V-OUT-ALARM:NO V-MAIN-ALARM:NO BATTERY-LOW:N/A
V-OUT:+12.1 V V-MAIN:+12.0 V V-BATT:+0.0 V
- Battery Charger ------------------------------------------------------
CHARGER:ENABLED CHARGING:NO
V-CHARGE:+13.9 V I-CHARGE:+0.0 A DUTY-CYCLE:50%
- Manual battery test result -------------------------------------------
TEST-ALLOWED:NO TEST-DELAY:N/A
LAST-RESULT:NOT-TESTED
LAST-EXECUTION:N/A
V-NO-LOAD:N/A V-START:N/A V-END:N/A
The meaning:
USB-STATE
State of the UPS:
DISCONNECTED
- The device is not
connected.
CONNECTED
- The device is
connected.
UPTIME
Uptime of the UPS. N/A
-
USB-STATE
is
DISCONNECTED
.
POWER-SOURCE
Power source:
MAIN
- The main power voltage is
present.
BATTERY
- The main power voltage is
not present.
N/A
- USB-STATE
is
DISCONNECTED
.
BATTERY
Battery condition:
NOT-PRESENT
- The battery isn't
present.
PRESENT
- The battery is
present.
PRESENT-TESTING
- The battery is
present and under testing.
N/A
- USB-STATE
is
DISCONNECTED
.
V-OUT-ALARM
The output regulated voltage is out of range:
NO
- The output regulated voltage is
in the proper range.
YES
- The output regulated voltage is
outside the proper range.
N/A
- USB-STATE
is
DISCONNECTED
.
V-MAIN-ALARM
The main voltage is out of range
NO
- The main voltage is in the
proper range.
YES
- The main voltage is outside the
proper range.
N/A
- USB-STATE
is
DISCONNECTED
.
BATTERY-LOW
The battery voltage is below the threshold:
NO
- The battery voltage is over the
battery low threshold.
YES
- The battery voltage is below
the threshold.
N/A
- USB-STATE
is
DISCONNECTED
or BATTERY
is NOT-PRESENT
.
V-OUT
Output regulated voltage value. N/A
-
USB-STATE
is
DISCONNECTED
.
V-MAIN
Main power source voltage. N/A
-
USB-STATE
is
DISCONNECTED
.
V-BATT
Battery voltage value measured when the battery charger is
disconnected. N/A
-
USB-STATE
is
DISCONNECTED
.
CHARGER
Charger state:
ENABLED
- The battery charger is
enabled.
DISABLED
- The battery charger is
disabled or the external voltage is too low to charge the
battery.
N/A
- USB-STATE
is
DISCONNECTED
.
CHARGING
Battery charging state:
NO
- The battery is not charging: the
battery charger is disconnected (CHARGER
is
DISABLED
) or the charging current
(I-CHARGE
) is less than ~200mA.
YES
- The battery is charging.
N/A
- USB-STATE
is
DISCONNECTED
.
V-CHARGE
Battery voltage value measured when the battery charger is
connected. N/A
- USB-STATE
is DISCONNECTED
.
I-CHARGE
Battery charge current. N/A
-
USB-STATE
is
DISCONNECTED
.
DUTY-CYCLE
Battery charging duty cycle:
0
- The battery charger is always
disconnected.
50
- The battery charger is connected
half of the time with a period of 4 seconds.
100
- The battery charger is
disconnected for 0.5 seconds every 60 seconds.
N/A
- USB-STATE
is
DISCONNECTED
.
TEST-ALLOWED
Inform if the test can be executed:
NO
- It isn't possible to execute the
test.
YES
- It is possible to execute the
test.
TESTING
- Test is already
ongoing.
N/A
- USB-STATE
is
DISCONNECTED
.
TEST-DELAY
Seconds before the DENIED
barrier is
removed. N/A
- USB-STATE
is
DISCONNECTED
.
LAST-RESULT
Result of the battery test:
NOT-TESTED
- Test results not
available: the test has not been executed yet.
SUCCESSFUL
- The battery passed the
test.
FAILED
- The battery fail the
test.
DENIED
- It is not possible to start
the battery test because there has been a switch to battery in
the last 24 hours (caused by a power failure or by a battery
test).
BATTERY-LOW
- It is not possible to
start the battery test because the battery voltage is too
low.
BATTERY-NOT-PRESENT
- It is not
possible to start the battery test because there isn't any
battery.
TESTING
- Test is running right
now.
N/A
- USB-STATE
is
DISCONNECTED
.
LAST-EXECUTION
Date and Time of last test execution. N/A
- USB-STATE
is
DISCONNECTED
.
V-NO-LOAD
Voltage of the battery before starting the test.
N/A
- USB-STATE
is
DISCONNECTED
or LAST-RESULT
is one of the following: NOT-TESTED
,
DENIED
, BATTERY-LOW
,
BATTERY-NOT-PRESENT
or
TESTING
.
V-START
Voltage of the battery after starting the test.
N/A
- USB-STATE
is
DISCONNECTED
or LAST-RESULT
is one of the following: NOT-TESTED
,
DENIED
, BATTERY-LOW
,
BATTERY-NOT-PRESENT
or
TESTING
.
V-END
Voltage of the battery when the test finish.
N/A
- USB-STATE
is
DISCONNECTED
or LAST-RESULT
is one of the following: NOT-TESTED
,
DENIED
, BATTERY-LOW
,
BATTERY-NOT-PRESENT
or
TESTING
.
This command can help to understand what is happening, in case of troubles:
[13:48:36] ABILIS_CPX:d s ups
RES:Ups -----------------------------------------------------------------------
Uninterruptable_Power_Supply_device
--- Cleared 41 days 21:08:34 ago, on 13/07/2017 at 14:50:51 ------------
-----------|---INPUT---|--OUTPUT---|-----------|---INPUT---|--OUTPUT---|
SW-SHUTDOWN| | 0|V-MAIN-ALM | 0| |
HW-SHUTDOWN| 0| |V-OUT-ALM | 0| |
BATT-LOW | 0| | | | |
V-MAIN-FAIL| 0| |LIVE | | 3618517|
CHARGE-DIS | 0| |LIVE-EXP | 0| |
------------------------------------------------------------------------
With reference to the shown interval of time («Cleared 41 days 21:08:34 ago») these counters show the number of:
SW-SHUTDOWN | V_OUT_HOST_SHUTDOWN received from the UPS. |
HW-SHUTDOWN | V_OUT_UPS_SHUTDOWN received from the UPS. |
BATT-LOW | BATTERY LOW received from the UPS. |
V-MAIN-FAIL | Failures of the MAIN power. |
CHARGE-DIS | BATTERY CHARGER disconnection received from the UPS. |
V-MAIN-ALM | V_MAIN_ALARM detected by the UPS. |
V-OUT-ALM | V_OUT_ALARM detected by the UPS. |
LIVE | LIVE received by the UPS. |
LIVE-EXP | Times the LIVE has expired in the UPS. |