This command reports the current situation of the device:
[13:42:55] ABILIS_CPX:d d gpio
RES:Gpio-1 --------------------------------------------------------------------
       STATE:UP             USB-STATE:CONNECTED      
       - Digital Input Lines State --------------------------------------------
        1..16| off off off off off off off off .   .   .   .   .   .   .   .   
       ------------------------------------------------------------------------
       - Digital Output Lines State -------------------------------------------
        1..16| off off off off .   .   .   .   .   .   .   .   .   .   .   .   
       ------------------------------------------------------------------------
       - Analog Input Lines ---------------------------------------------------
             | State  Value   Unit     ADC    | State  Value   Unit     ADC
       ------+--------------------------------+--------------------------------
        1.. 2| NORMAL     10  C        0      | NORMAL    0.0  %        0      
        3.. 4| .           .  .        .      | .           .  .        .      
        5.. 6| .           .  .        .      | .           .  .        .      
        7.. 8| .           .  .        .      | .           .  .        .      
       ------------------------------------------------------------------------The meaning:
STATEGPIO driver state:
DOWN - device stopped or
                  disconnected.
UP - device running.
INACTIVE - device good, but
                  inactive (configuration parameter
                  ACT:NO).
USB-STATEUSB device connection state:
DISCONNECTED - device disconnected
                  from USB port.
CONNECTED - device
                  connected.
D-IN:1...8 / D-OUT:1...4GPIO digital input/output line state:
OFF - logical 0 state.
ON - logical 1 state.
N/A (not available) - unknown
                  state.
StateGPIO analog input line state:
LOW - under the low
                  threshold.
NORMAL - between high and low
                  threshold.
HIGH - between high and low
                  threshold.
N/A (not available) - unknown
                  state.
ValueGPIO analog input line value. N/A (not
              available) - unknown state.
UnitUnit for analog input/output lines.
ADCConverted value from ADC value on analog input/output lines.
This command can help to understand what is happening, in case of troubles:
[13:48:36] ABILIS_CPX:d s gpio 
RES:Gpio-1 --------------------------------------------------------------------
       --- Cleared 13 days 21:06:37 ago, on 11/08/2017 at 18:08:13 ------------
       -----------|---INPUT---|--OUTPUT---|-----------|---INPUT---|--OUTPUT---|
       USB-CONN   |         67|           |USB-DISC   |           |         66|
       USB-AUTRST |          0|           |           |           |           |
       CHR        |   17650515|   13290463|FRM        |    2777250|    2777271|
       ------------------------------------------------------------------------With reference to the shown interval of time («Cleared 13 days 21:06:37 ago») these counters show the number of:
| USB-CONN | USB connections. | 
| USB-DISC | USB disconnections. | 
| USB-AUTRST | USB autorestarts. Troubles on USB interface. | 
| CHR | Bytes in received/transmitted frames. | 
| FRM | Received/transmitted frames. | 
This command reports the current situation of the device:
[13:42:55] ABILIS_CPX:d d mfio
RES:MfIo ----------------------------------------------------------------------
       Abilis_Multi_Function_IO_Interface                                      
       STATE:ACTIVE
       - Digital Input Lines State --------------------------------------------
        1..7| off off off off off off off 
       ------------------------------------------------------------------------
       - Digital Output Lines State -------------------------------------------
        1..7| off off off off off off off 
       ------------------------------------------------------------------------The meaning:
STATEMFIO driver state:
ACTIVE - device running.
INACTIVE - device good, but
                  inactive (configuration parameter
                  ACT:NO).
D-IN:1...7 / D-OUT:1...7MFIO digital input/output line state:
OFF - logical 0 state.
ON - logical 1 state.
N/A (not available) - unknown
                  state.
This command can help to understand what is happening, in case of troubles:
[13:48:36] ABILIS_CPX:d s mfio 
RES:MfIo ----------------------------------------------------------------------
       Abilis_Multi_Function_IO_Interface                                      
       --- Cleared 0 days 13:21:08 ago, on 25/08/2017 at 02:02:40 -------------
       -----------|---INPUT---|--OUTPUT---|-----------|---INPUT---|--OUTPUT---|
       IRQ        |         35|           |           |           |           |
       STATE      |          2|           |ERR-STATE  |          0|           |
       LINE-STATE |         63|           |ERR-LINE-ST|          0|           |
       ALARM      |         63|           |ERR-ALARM  |          0|           |
       ------------------------------------------------------------------------With reference to the shown interval of time («Cleared 0 days 13:21:08 ago») these counters show the number of:
| IRQ | MFIO interrupts. | 
| STATE | Set State requests. | 
| LINE-STATE | Set Line State requests. | 
| ALARM | Set Alarm requests. | 
| ERR-STATE | Errors during Set State. | 
| ERR-LINE-ST | Errors during Set Line State. | 
| ERR-ALARM | Errors during Set Alarm. | 
| ![[Note]](../images/note.png) | Note | 
|---|---|
| If you notice incrementation of  | 
This command reports the current situation of the device:
[13:42:55] ABILIS_CPX:d d rvs
RES:Rvs-1 ---------------------------------------------------------------------
       STATE:UP                   MAC:B8-27-EB-93-FA-DF
       RemAdd-RemPort:192.168.029.101-41414
       CURRENT-IMAGE:5.000        FACTORY-IMAGE:5.000     BOARD:0.0
       - Digital Input Lines State --------------------------------------------
        1.. 4| ON  ON  ON  ON  
       ------------------------------------------------------------------------
       - Digital Output Lines State -------------------------------------------
        1.. 4| off ON  off off 
       ------------------------------------------------------------------------
       - Cameras diagnostics --------------------------------------------------
       CAM:  State:    LIVE: LIVE-REC: ALARM-REC: STORED-ALARMS: STORED-LIVE:
       ------------------------------------------------------------------------
       Cam-1 UP        0     NO        NO         54             0
       ------------------------------------------------------------------------The meaning:
STATERVS driver state:
DOWN - device is down.
UP - device is active and
                  ready.
INACTIVE - device is
                  inactive.
MACRVS device driver MAC address.
RemAdd-RemPortRemote IP address and remote port.
CURRENT-IMAGECurrent image version.
FACTORY-IMAGEFactory image version.
D-IN:1...4 / D-OUT:1...4RVS digital input/output line state:
OFF - logical 0 state.
ON - logical 1 state.
. (not available) - unknown
                  state.
This command can help to understand what is happening, in case of troubles:
[13:48:36] ABILIS_CPX:d s rvs 
RES:Rvs-1 ---------------------------------------------------------------------
       --- Cleared 0 days 14:12:29 ago, on 25/08/2017 at 02:02:39 -------------
       -----------|---INPUT---|--OUTPUT---|-----------|---INPUT---|--OUTPUT---|
       CONN-SUCC  |           |          1|BOARD-ERR  |          0|           |
       CONN-FAIL  |           |          0|           |           |           |
       CLOSE      |          0|          0|           |           |           |
       CFG-FAIL   |          0|           |SET-AO-CUT |          0|           |
       SET-FAIL   |           |          0|           |           |           |
       PROT-ERR   |          0|          0|           |           |           |
       IMAGE-ERR  |          0|           |           |
       ------------------------------------------------------------------------With reference to the shown interval of time («Cleared 0 days 14:12:29») these counters show the number of:
| CONN-SUCC | Successful opened sessions, at least a response received. | 
| CONN-FAIL | Aborted sessions (on opening), TCP failed or no response received. | 
| CFG-FAIL | Failed configuration of digital/analog parameters. | 
| SET-FAIL | Failed setting of digital/analog outputs. | 
| PROT-ERR | JMUX Errors. | 
| BOARD-ERR | Connections aborted on Missing board. | 
| SET-AO-CUT | Setting of analog outputs that where cutted. | 
| ![[Note]](../images/note.png) | Note | 
|---|---|
| If you notice incrementation of these counters consult Abilis support (tem@antek.it). | 
This command reports the current situation of the device:
[13:42:55] ABILIS_CPX:d d rio
RES:Rio-1 ---------------------------------------------------------------------
       RIO                                                                     
       STATE:UP                   MAC:B8-27-EB-12-F7-FB
       RemAdd-RemPort:192.168.001.222-41414
       CURRENT-IMAGE:5.001        FACTORY-IMAGE:5.001     BOARD:1.6
       - Digital Input Lines State --------------------------------------------
        1.. 8| ON  ON  ON  ON  ON  ON  ON  ON  
       ------------------------------------------------------------------------
       - Digital Output Lines State -------------------------------------------
        1.. 8| off off off off off off off off 
       ------------------------------------------------------------------------
       - Analog Input Lines ---------------------------------------------------
             | State  Value   Unit     ADC    | State  Value   Unit     ADC
       ------+--------------------------------+--------------------------------
        1.. 2| NORMAL   50.0  %        2048   | NORMAL   50.0  %        2048   
        3.. 4| NORMAL   50.0  %        2048   | NORMAL   50.0  %        2048   
       ------------------------------------------------------------------------
       - Analog Output Lines --------------------------------------------------
             | State  Value   Unit     ADC    | State  Value   Unit     ADC
       ------+--------------------------------+--------------------------------
        1.. 2| NORMAL    0.0  %        0      | NORMAL    0.0  %        0      
        3.. 4| NORMAL    0.0  %        0      | NORMAL    0.0  %        0      
       ------------------------------------------------------------------------The meaning:
STATERIO driver state:
DOWN - device is down.
UP - device is active and
                  ready.
INACTIVE - device is
                  inactive.
MACRIO device driver MAC address.
RemAdd-RemPortRemote IP address and remote port.
CURRENT-IMAGECurrent image version.
FACTORY-IMAGEFactory image version.
D-IN:1...8 / D-OUT:1...8RIO digital input/output line state:
OFF - logical 0 state.
ON - logical 1 state.
. (not available) - unknown
                  state.
StateRIO analog input/output line state:
LOW - under the low
                  threshold.
NORMAL - between high and low
                  threshold.
HIGH - between high and low
                  threshold.
. (not available) - unknown
                  state.
ValueRIO analog input line value. N/A (not
              available) - unknown state.
UnitUnit for analog input/output lines.
ADCConverted value from ADC value on analog input/output lines.
This command can help to understand what is happening, in case of troubles:
[13:48:36] ABILIS_CPX:d s rio 
RES:Rio-1 ---------------------------------------------------------------------
       RIO                                                                     
       --- Cleared 17 days 01:07:47 ago, on 08/08/2017 at 15:19:38 ------------
       -----------|---INPUT---|--OUTPUT---|-----------|---INPUT---|--OUTPUT---|
       CONN-SUCC  |           |          1|BOARD-ERR  |          0|           |
       CONN-FAIL  |           |          0|           |           |           |
       CLOSE      |          0|          0|           |           |           |
       CFG-FAIL   |          0|           |SET-AO-CUT |          0|           |
       SET-FAIL   |           |          0|           |           |           |
       PROT-ERR   |          0|          0|           |           |           |
       ------------------------------------------------------------------------With reference to the shown interval of time («Cleared 17 days 01:07:47 ago») these counters show the number of:
| CONN-SUCC | Successful opened sessions, at least a response received. | 
| CONN-FAIL | Aborted sessions (on opening), TCP failed or no response received. | 
| CFG-FAIL | Failed configuration of digital/analog parameters. | 
| SET-FAIL | Failed setting of digital/analog outputs. | 
| PROT-ERR | JMUX Errors. | 
| BOARD-ERR | Connections aborted on Missing board. | 
| SET-AO-CUT | Setting of analog outputs that where cutted. | 
| ![[Note]](../images/note.png) | Note | 
|---|---|